Model S3KS
Phase 1 phase 2 wire PE
Capacity 3kVA/2.4KW
Input
Nominal Input Voltage 220/230/240VAC
Input Voltage Range 110V-300V@Halfload
176V-300V@Full Load
Input Frequency Range 40-70Hz
Input Power Factor 0.99@Full load
Output
Output Voltage 230V(208/220/240/Selectable)
Voltage Regulation 1%
Output Frequency (Sync.Mode / Bat.Mode) 47Hz-53Hz; 57Hz-63Hz / 50Hz /-0.05Hz 60Hz /-0.05Hz
Output THDv% 1.5% linear Load 4.5% Non-linear Load
Output Waveform Pure Sinewave
Transfer Time
Line mode -- Bat Mode 0ms
Inv -- Bypass Mode <4ms
Efficiency
AC--AC 91%
ECO 96%
Battery Mode 89%
Battery & Charger
Battery Voltage/Capacity 72V / 96V external BAT
Battery Type Valve Regulated Maintenance Free Lead Acid (VRLA) for Standard Model with internal battery
Recharge time Subject to external BAT
Max recharge current 6A
Floating charge Voltage 81.8V/109.2V
Display
Display LED/LCD
Buzzer Alarm Bat.Mode/Bat.Low/OverLoad/Fault
Physical
Dimension 145(W)*220(H)*328(L)mm
Weight 10.8kg
Environment
Humidity 5-97%(Non condensing )
Operating Ambient temperature 0-40℃
Communication Port NS232/SNMP(option)/USB(option)


 


 


 